MIL-PRF-12048E
d. Free water and particulate contamination in distillate fuels per ASTM D 4176
(Procedure1)
e. Fuel temperature per API-MPMS Chapter 7 Section 1
3.4.2 Government furnished property. The following item, one per kit, will be furnished by
the Government.
Sampling and Gaging Kit, Petroleum: PortableNSN 6680-00-151-5310
The sampling and gaging kit (23 cm x 23 cm x 39.4 cm; 10 kg) shall fit within and be an integral
component of the ground fuels test kit.
3.4.3 Power connection. The electrically operated components of the kit shall use 115Vac, ±
10%, 60 Hz, ± 2% and shall conform to the requirements of the National Electrical Code,
NFPA 70. All electrically operated components shall be UL approved.
3.4.4 Container. The kit components shall be contained in a container. The container shall be
fabricated so that it can be raised and locked into working position; and lowered and locked for
transit or storage. In its working position, the top of the kit shall provide a flat, horizontal surface
with a minimum of 1 sq. meter and a height of 91 ± 10 cm. Partitions or other suitable means to
block the wind from the work area shall be provided. Components within the container shall be
securely restrained, and adequately cushioned to prevent damage during transit.
3.4.4.1 Envelope. The overall dimensions of the container, in storage or transit configuration,
shall not be greater than 91.5 cm (36.0 inches) long × 53.5 cm (21.0 inches) deep × 63.5 cm (25.0
inches) high.
3.4.4.2 Weight. The weight of the kit shall not exceed 89 kg (196 pounds).
3.4.4.3 Stowable handles. The design of the container shall incorporate handles, or other
suitable means, for grasping, handling, and carrying by four persons wearing appropriate
protective clothing. The handles shall retract or fold within the envelope of the container when
not in use.
3.5 Test kit loading diagram. A diagram shall be provided to identify equipment placement in
the container. The loading diagram shall be permanently affixed to the inside of the kit's cover to
easily identify storage locations. The loading diagram shall be legible for the life of the kit.
3.6 Environmental requirements.
3.6.1 Climatic. The kit shall be capable of performing in any ambient temperature from -25°C
to 50°C. When placed in storage, the test kit shall not be damaged in any ambient temperature
from -33°C to 63°C (see 4.5.2).
3.6.2 Fungus Resistance. Components susceptible to fungus and moisture damage shall be
treated for protection.
3.6.3 Visibility. The kit shall contain a light source for performing tests in poorly lit areas.
3.6.4 Water Resistance. The container shall not allow any water leakage.
4
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business